Automatic Reset, Manual Reset, Fan Cycle, Vacuum Regulating.
Factory preset set-points, SPST / SPDT ( NO / NC )
|
|

| Automatic Reset Pressure Control (.pdf)
Pressure range: | 0 to 700 PSIG (0 to 48,2 Bar)
| Burst: | 5,000 PSI (344,8 Bar)
| Proof: | < 100 (< 6,9 Bar) = 250 PSIG (17,2 Bar), < 500
(< 34,4 Bar) = 600 PSIG (41,4 Bar),
> 500 (> 34,4 Bar) = 800 PSIG (55,2 Bar)
| Voltage: | 24 VAC – 125 VA Pilot Duty, 120/240 VAC – 375 VA Pilot Duty, 120/240 VAC – 6 FLA, 36 LRA
| Life at rated load: | 100,000 cycles
|
| 
| Manual Reset Pressure Control (.pdf)
Pressure range: | 200 to 700 PSIG (14 to 48,2 Bar)
| Burst: | 6,000 PSI (413,8 Bar)
| Proof: | < 500 (< 34,4 Bar) = 600 PSIG (41,4 Bar),
> 500 (> 34,4 Bar) = 800 PSIG (55,2 Bar)
| Voltage: | 24 VAC – 125 VA Pilot Duty, 120/240 VAC – 375 VA Pilot Duty, 120/240 VAC – 6 FLA, 36 LRA
| Life at rated load: | 6,000 cycles
|
| 
| Fan Cycle Switch (.pdf)
Pressure range: | 0 to 700 PSIG (0 to 48,2 Bar)
| Burst: | 5,000 PSI (344,8 Bar)
| Proof: | < 100 (< 6,9 Bar) = 250 PSIG (17,2 Bar),
< 500 (< 34,4 Bar) = 600 PSIG (41,4 Bar),
> 500 (> 34,4 Bar) = 800 PSIG (55,2 Bar)
| Voltage: | 24 VAC – 125 VA Pilot Duty, 120/240 VAC – 375 VA Pilot Duty, 120/240 VAC – 6 FLA, 36 LRA
| Life at rated load: | 100,000 cycles
| | 
| Vacuum Regulating Switch (.pdf)
Pressure range: | 25 in Hg to 25 PSIG (-0,86 to 1,7 Bar)
| Burst: | 5,000 PSI (344,8 Bar)
| Proof: | 250 PSIG (17,2 Bar)
| Voltage: | 24 VAC – 125 VA Pilot Duty, 120/240 VAC – 375 VA Pilot Duty, 120/240 VAC – 6 FLA, 36 LRA
| Life at rated load: | 100,000 cycles
| |
A complete line of Texas Instruments
pressure controls is also available. Please contact
for more information.
|