Automatic Reset, Manual Reset, Fan Cycle, Vacuum Regulating.
Factory preset set-points, SPST / SPDT ( NO / NC )


Automatic Reset Pressure Control (.pdf)
Pressure range: 0 to 700 PSIG (0 to 48,2 Bar)
Burst: 5,000 PSI (344,8 Bar)
Proof: < 100 (< 6,9 Bar) = 250 PSIG (17,2 Bar), < 500
(< 34,4 Bar) = 600 PSIG (41,4 Bar), > 500 (> 34,4 Bar) = 800 PSIG (55,2 Bar)
Voltage: 24 VAC 125 VA Pilot Duty, 120/240 VAC 375 VA Pilot Duty, 120/240 VAC 6 FLA, 36 LRA
Life at rated load: 100,000 cycles

Manual Reset Pressure Control (.pdf)
Pressure range: 200 to 700 PSIG (14 to 48,2 Bar)
Burst: 6,000 PSI (413,8 Bar)
Proof: < 500 (< 34,4 Bar) = 600 PSIG (41,4 Bar), > 500 (> 34,4 Bar) = 800 PSIG (55,2 Bar)
Voltage: 24 VAC 125 VA Pilot Duty, 120/240 VAC 375 VA Pilot Duty, 120/240 VAC 6 FLA, 36 LRA
Life at rated load: 6,000 cycles

Fan Cycle Switch (.pdf)
Pressure range: 0 to 700 PSIG (0 to 48,2 Bar)
Burst: 5,000 PSI (344,8 Bar)
Proof: < 100 (< 6,9 Bar) = 250 PSIG (17,2 Bar),
< 500 (< 34,4 Bar) = 600 PSIG (41,4 Bar), > 500 (> 34,4 Bar) = 800 PSIG (55,2 Bar)
Voltage: 24 VAC 125 VA Pilot Duty, 120/240 VAC 375 VA Pilot Duty, 120/240 VAC 6 FLA, 36 LRA
Life at rated load: 100,000 cycles

Vacuum Regulating Switch (.pdf)
Pressure range: 25 in Hg to 25 PSIG (-0,86 to 1,7 Bar)
Burst: 5,000 PSI (344,8 Bar)
Proof: 250 PSIG (17,2 Bar)
Voltage: 24 VAC 125 VA Pilot Duty, 120/240 VAC 375 VA Pilot Duty, 120/240 VAC 6 FLA, 36 LRA
Life at rated load: 100,000 cycles

A complete line of Texas Instruments pressure controls is also available. Please contact for more information.


For your convenience we accept:

For Ordering, contact Intertech at:1-954-602-2000